6 Wiring
6.4.7 Operating Conditions on 400-V Power Supply Voltage
6-30
6.4.7 Operating Conditions on 400-V Power Supply Voltage
There are four types of SGDH SERVOPACKs, for the power supply voltages: Single-phase 100 VAC, single-
phase 200 VAC, three-phase 200 VAC, and three-phase 400 VAC. When using the SERVOPACK for 100 V or
200 V with the three-phase 400-VAC class (380 to 480 V), prepare the following voltage conversion transform-
ers (single-phase or three-phase)
When selecting a voltage conversion transformer, refer to the capacities shown in the following table.
* This is the net value at the rated load.
• Do not connect the SERVOPACK for 100 V and 200 V directly to a voltage of 400 V.
The SERVOPACK will be destroyed.
• Control the AC power supply ON and OFF sequence at the primary side of voltage conversion transfer.
Voltage conversion transfer inductance will cause a surge voltage if the power is turned ON and OFF at the secondary,
damaging the SERVOPACK.
CAUTION
Primary Voltage
Secondary Voltage
380 to 480 VAC
380 to 480 VAC
→
→
200 VAC
100 VAC
Voltage
SERVOPACK Model
SGDH-
Voltage Capacity per
SERVOPACK * (kVA)
Current Capacity of Circuit
Breaker or Fuse (Arms)
Single-phase
100 V
A3BE
0.15
4
A5BE
0.25
01BE
0.40
02BE
0.60
6
Single-phase
200 V
A3AE
0.20
4
A5AE
0.25
01AE
0.40
02AE
0.75
04AE
1.2
8
Single-phase
220 V
08AE-S
2.1
11
15AE-S
4.0
19
Three-phase
200 V
05AE
1.4
4
08AE
1.9
7
10AE
2.3
15AE
3.2
10
20AE
4.3
13
30AE
5.9
17
50AE
7.5
28
60AE
12.5
32
75AE
15.5
41
1AAE
22.7
60
1EAE
30.9
81