5 Specifications and Dimensional Drawings of Cables and Peripheral Devices
5.8.9 Molded-case Circuit Breaker (MCCB)
5-74
(2) Specifications
(3) Precautions
Circuit Breakers
• Select a breaker for inverters.
• High-frequency current leaks from the servomotor armature because of switching operations inside the SER-
VOPACK.
(a) Maximum Input Current
• The instantaneous maximum output of SERVOPACK is approximately 3 times of the rated output for
maximum 3 seconds. Accordingly, select a circuit breaker whose operating time is 5 seconds or more at
300% of SERVOPACK rated current.
The general-purpose and low-speed acting molded-case circuit breakers are applicable.
• The power supply capacity per SERVOPACK when using a servomotor is described in
2.6.2 Molded-case
Circuit Breaker and Fuse Capacity
. Select a circuit breaker with the capacity larger than the effective
load current (when using multiple SERVOPACKs) calculated from the total power supply capacity.
• The power consumption of other controllers must be considered when selecting a circuit breaker.
(b) Inrush Current
• Refer to
2.6.2 Molded-case Circuit Breaker and Fuse Capacity
for SERVOPACK inrush current.
• The allowable inrush current for a low-speed acting circuit breaker is approximately 10 times of the rated
current for 0.02 seconds.
• When turning ON multiple SERVOPACKs simultaneously, select a molded-case circuit breaker with the
allowable current for 20 ms larger than the total inrush current shown in
2.6.2 Molded-case Circuit
Breaker and Fuse Capacity
.
Phase
3
φ
3W
Number of Poles
3
Rated Voltage
Common for 100 V/200 V/415 VAC
Rated Current and
Motor Rated Capacity under
Basic Ambient Temperature of 40
°
C
(104
°
F)
Rated
Current
A
kW
Rated
Current
A
kW
200 V
415 V
200 V
415 V
45
11
22
(8)
-
3.7
(40)
-
18.5
7.1
1.5
-
32
7.5
15
(5)
-
2.2
25
5.5
11
4
0.75
1.5
16
3.7
7.5
2.5
0.4
-
(12)
-
5.5
(2)
-
0.75
10
2.2
-
1.4
0.2
-
Rated Current Sensitivity
30 mA, 100 (200 or 500 switchable)
Operating Time
Within 0.1 s
Ground Fault Display Method
Mechanical button
Rated Interrupt-
ing Current
JIS C8371
415 VAC
2.5 kA
200 VAC
5 kA
100 VAC
5 kA
IMPORTANT