11.2 Connection to Host Controller
11-25
11
11.2.10 Example of Connection to MITSUBISHI’s AD75 Positioning Unit
(SERVOPACK in Position Control Mode)
* The ALM signal is output for about two seconds when the power is turned ON. Take this into consider-
ation when designing the power ON sequence. The ALM signal actuates the alarm detection relay 1Ry
to stop the main circuit power supply to the SERVOPACK.
Note: Only signals applicable to Mitsubishi’s AD75 Positioning Unit and Yaskawa’s SGDH SERVO-
PACK are shown in the diagram.
+
-
+24V
024V
1Ry
CN1
CN1
STOP
DOG
READY
PGO
PULSE
SIGN
CLEAR
1Ry
2.2K
19
14
15
12
8
7
32
31
20
42
43
40
47
/S-ON
P-OT
N-OT
25
24
14
7
26
23
5
22
4
21
3
+24 V
0
24
V
+24V
PULS
CLR
SIGN
/PULS
/CLR
/SIGN
ALM+
ALM -
PCO
/PCO
Positioning unit AD75
manufactured by
Mitsubishi
I/O power supply
X-axis (Y-axis)
SGDH SERVOPACK
ON when
proximity is
detected.
ON when
positioning is
canceled.
11
11
CN2
L1C
L3
L2
L1
L2C
W
V
A(1)
B(2)
C(3)
D(4)
U
Servomotor
M
Control
power supply
Main circuit
power supply
PG