Protective Elements
Parameter
Description
Setting range
Default
Menu path
Shots
Maximum number of permitted reclosure
attempts.
1 - 6
1
[Protection
Para
/<1..4>
/AR
/General
Settings]
Initiate Mode
Initiate Mode
Alarm,
TripCmd
Alarm
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-start
Start timer - While the start timer runs
down, an AR attempt can be started. Only if
the trip command is given within the start
time/duration an AR attempt could be
started. The location and the resistance of
the fault have a big influence on the tripping
time. The start time has an impact on
whether an AR attempt should be started
when the fault is far away or high
resistance.
Only available if: Initiate Mode = TripCmd
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-DP1
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 1-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl1]
t-DP2
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 2-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl2]
t-DP3
Dead time between trip and reclosure
attempt for phase faults.
Only available if: Shots = 3-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl3]
531
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...