Protective Elements
Parameter
Description
Setting range
Default
Menu path
Char
Characteristic
DEFT,
INV
DEFT
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.00s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
K
This setting is the negative sequence
capability constant. This value is normally
provided by the generator manufacturer.
Only available if: Characteristic = INV
1.00 - 200.00s
10.0s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
τ-cool
If the unbalanced load current falls below
the pickup value, the cooling-off time is
taken into account. If the unbalanced load
exceeds the pickup value again, than the
saved heat within the electrical equipment
will lead to an accelerated trip.
Only available if: Characteristic = INV
0.0 - 60000.0s
0.0s
[Protection
Para
/<1..4>
/I-Prot
/I2>[1]]
Current Unbalance Module Input States
Name
Description
Assignment via
ExBlo1-I
Module input state: External blocking1
[Protection Para
/Global Prot Para
/I-Prot
/I2>[1]]
ExBlo2-I
Module input state: External blocking2
[Protection Para
/Global Prot Para
/I-Prot
/I2>[1]]
ExBlo TripCmd-I
Module input state: External Blocking of the Trip
Command
[Protection Para
/Global Prot Para
/I-Prot
/I2>[1]]
483
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...