Acknowledgments
Manual Acknowledgment
It is possible to acknowledge LEDs, SCADA, binary output relays and / or a pending trip command by pressing the
»C« key at the panel.
There are two principles available how the »C« key shall react when being pressed:
•
(1.)
With intermediate selection step: After the »C« key has been pressed, you select the items to be
acknowledged (LEDs, SCADA, binary output relays, trip command, or all of these) via the Softkeys. After
this, you press the Softkey with the »Wrench-Symbol«.
•
(2.)
Immediate acknowledge: After it has been configured which items shall be be assigned to the »Ack via
»C« key«, these are acknowledged by simply pressing the »C« key (for ca. 1 second).
The setting parameter [Device Para / Acknowledge]
»Ack via »C« key« decides about which principle described
above shall be available when the »C« key is pressed:
•
“Nothing” – Pressing the »C« key works as described with “principle (1.)“, i. e. you explicitly select the
items to be acknowledged.
•
“Ack LEDs” – Pressing the »C« key (for approx. 1 second) acknowledges all LEDs immediately (only
the password will be asked for, see below).
•
“Ack LEDs, relays” – Pressing the »C« key (for approx. 1 second) acknowledges all LEDs and all binary
output relays immediately (only the password will be asked for, see below).
•
“Ack Everything” – Pressing the »C« key (for approx. 1 second) acknowledges all (above) mentioned
items immediately (only the password will be asked for, see below).
The three immediate types of acknowledgments according to “principle (2.)“ can be recognized from the fact that it
always includes an LED test, i. e. all LEDs flash in red color for a second, then flash in green color for a second.
Independent of which acknowledgment type you have set, note that you are
asked to enter the password.
If there is the need to be able to acknowledge without entering any password
set an empty password for the level
»Prot-Lv1«.
For general information about passwords and security-related considerations,
see the „Security“ chapter.
159
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...