Installation and Connection
Assembly Groups
In line with the customer’s requirement the devices are combined in a
modular way (in compliance with the order code). In each of the slots an
assembly-group may be integrated. In the following the terminal
assignment of the individual assembly-groups are shown. The exact
installation place of the individual modules can be learned from the
connection diagram fixed at the top of your device.
Housing B1
B1 housing – schematic diagram
Grounding
The housing must be carefully grounded. Connect a ground cable
(protective earth, 4 to 6 mm
2
[AWG 11‒9], tightening torque 1.7 Nm
[15
lb⋅in
]) to the housing, using the screw that is marked with the ground
symbol (at the rear side of the device).
Moreover, the power supply card needs a separate ground connection
(functional earth, min. 2.5 mm
2
[≤ AWG 13], tightening torque 0,56 ‒
0,79 Nm [5‒7
lb⋅in
]). See the “Terminal Marking” diagram in Section “DI-4
X – Power Supply and Digital Inputs” to check for the correct terminal.
All grounding connections (i. e. protective and functional earth) must be
low-inductance, i. e. as short as possible, and national standards – if
applicable – must be followed.
The devices are very sensitive to electro-static discharges.
31
MRI4
DOK-HB-MRI4-2E
X1
X2
X3
slot1
slot2
slot3
X100
X
10
1
X103
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...