Communication Protocols
Modbus
®
Modbus
Modbus
®
Protocol Configuration
The time-controlled Modbus
®
protocol is based on the Master-Slave working principle. This means that the
substation control and protection system sends an enquiry or instruction to a certain device (slave address) which
will then be answered or carried out accordingly. If the enquiry/instruction cannot be answered/carried out (e.g.
because of an invalid slave address), a failure message is returned to the master.
The Master (substation control and protection system) can query information from the device, such as:
Type of unit version
Measuring values/Statistical measured values
Switch operating position
State of device
Time and date
State of the device’s digital inputs
Protection-/State alarms
The Master (control system) can give commands/instructions to the device, such as:
Control of switchgear (where applicable, i.e. each acc. to the applied device version)
Change-over of parameter set
Reset and acknowledgement of alarms/signals
Adjustment of date and time
Control of alarm relays
For detailed information on data point lists and error handling, please refer to the Modbus
®
documentation.
To allow configuration of the devices for Modbus
®
connection, some default values of the control system must be
available.
190
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...