Protective Elements
Parameter
Description
Setting range
Default
Menu path
Blo TripCmd
Permanent blocking of the Trip Command of
the module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
ExBlo TripCmd
Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo TripCmd
Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
IG Source
Selection if measured or calculated ground
current should be used.
sensitive
measurement,
measured,
calculated
calculated
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
Measuring
method
Measuring method: fundamental or rms or
3rd harmonic (only generator protection
relays)
Fundamental,
True RMS
Fundamental [Protection
Para
/<1..4>
/I-Prot
/IG[1]]
Meas Circuit
Superv
Activates the use of the measuring circuit
supervision. In this case the module will be
blocked if a measuring circuit supervision
module (e.g. LOP, VTS) signals a disturbed
measuring circuit (e.g. caused by a fuse
failure).
Only available if "VX Source" ist set to
"calculated".
inactive
inactive
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
IG>
If the pickup value is exceeded, the
module/stage will be started.
0.02 - 20.00In
0.02In
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
IGs>
If the pickup value is exceeded, the
module/stage will be started.
0.002 - 2.000In 0.02In
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
473
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...