Switchgear/Breaker – Manager
Parameter
Description
Setting range
Default
Menu path
Current2
Interrupted Current Level #2
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
1.20kA
[Control
/SG
/SG[1]
/SG Wear]
Count2
Open Counts Allowed #2
Only available if:SGwear Curve Fc = active
1 - 32000
10000
[Control
/SG
/SG[1]
/SG Wear]
Current3
Interrupted Current Level #3
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
8.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count3
Open Counts Allowed #3
Only available if:SGwear Curve Fc = active
1 - 32000
150
[Control
/SG
/SG[1]
/SG Wear]
Current4
Interrupted Current Level #4
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count4
Open Counts Allowed #4
Only available if:SGwear Curve Fc = active
1 - 32000
12
[Control
/SG
/SG[1]
/SG Wear]
Current5
Interrupted Current Level #5
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
Count5
Open Counts Allowed #5
Only available if:SGwear Curve Fc = active
1 - 32000
1
[Control
/SG
/SG[1]
/SG Wear]
Current6
Interrupted Current Level #6
Only available if:SGwear Curve Fc = active
0.00 -
2000.00kA
20.00kA
[Control
/SG
/SG[1]
/SG Wear]
390
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...