Input, Output and LED Settings
DI-8P X
DI Slot X1
Device Parameters of the Digital Inputs on DI-8P X
Parameter
Description
Setting range
Default
Menu path
Nom voltage
Nominal voltage of the digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Inverting 1
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Debouncing
time 1
A change of the state of a digital input will
only be recognized after the debouncing
time has expired (become effective). Thus,
transient signals will not be misinterpreted.
no debouncing
time,
20 ms,
50 ms,
100 ms
no
debouncing
time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 1]
Nom voltage
Nominal voltage of the digital inputs
24 V DC,
48 V DC,
60 V DC,
110 V DC,
230 V DC,
110 V AC,
230 V AC
24 V DC
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Inverting 2
Inverting the input signals.
inactive,
active
inactive
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
Debouncing
time 2
A change of the state of a digital input will
only be recognized after the debouncing
time has expired (become effective). Thus,
transient signals will not be misinterpreted.
no debouncing
time,
20 ms,
50 ms,
100 ms
no
debouncing
time
[Device Para
/Digital Inputs
/DI Slot X1
/Group 2]
77
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...