General Lists
Name
Description
SG[1].Aux OFF-I
Module input state: Position indicator/check-back signal of the CB (52b)
SG[1].Ready-I
Module input state: CB ready
SG[1].Sys-in-Sync-I
State of the module input: This signals has to become true within the synchronization
time. If not, switching is unsuccessful.
SG[1].Removed-I
State of the module input: The withdrawable circuit breaker is Removed
SG[1].Ack TripCmd-I
State of the module input: Acknowledgement Signal (only for automatic
acknowledgement) Module input signal
SG[1].Interl ON1-I
State of the module input: Interlocking of the ON command
SG[1].Interl ON2-I
State of the module input: Interlocking of the ON command
SG[1].Interl ON3-I
State of the module input: Interlocking of the ON command
SG[1].Interl OFF1-I
State of the module input: Interlocking of the OFF command
SG[1].Interl OFF2-I
State of the module input: Interlocking of the OFF command
SG[1].Interl OFF3-I
State of the module input: Interlocking of the OFF command
SG[1].SCmd ON-I
State of the module input: Switching ON Command, e.g. the state of the Logics or the
state of the digital input
SG[1].SCmd OFF-I
State of the module input: Switching OFF Command, e.g. the state of the Logics or
the state of the digital input
SG[1].Operations Alarm Signal: Service Alarm, too many Operations
SG[1].Isum Intr trip: IL1
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL1
SG[1].Isum Intr trip: IL2
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL2
SG[1].Isum Intr trip: IL3
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded: IL3
SG[1].Isum Intr trip
Signal: Maximum permissible Summation of the interrupting (tripping) currents
exceeded in at least one phase.
SG[1].Res TripCmd Cr
Signal: Resetting of the Counter: total number of trip commands
SG[1].Res Sum trip
Signal: Reset summation of the tripping currents
SG[1].WearLevel Alarm
Signal: Threshold for the Alarm
SG[1].WearLevel
Lockout
Signal: Threshold for the Lockout Level
SG[1].Res CB OPEN
capacity
Signal: Reset of the wear maintenance curve (i. e. of the counter for the Circuit
Breaker OPEN capacity.
SG[1].Isum Intr ph Alm
Signal: Alarm, the per hour Sum (Limit) of interrupting currents has been exceeded.
SG[1].Res Isum Intr ph
Alm
Signal: Reset of the Alarm, "the per hour Sum (Limit) of interrupting currents has
been exceeded".
IH2.active
Signal: active
IH2.ExBlo
Signal: External Blocking
IH2.Blo L1
Signal: Blocked L1
IH2.Blo L2
Signal: Blocked L2
IH2.Blo L3
Signal: Blocked L3
IH2.Blo IG meas
Signal: Blocking of the ground (earth) protection module (measured ground current)
IH2.Blo IG calc
Signal: Blocking of the ground (earth) protection module (calculated ground current)
648
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...