Protective Elements
Device Planning Parameters of the Inrush Module
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
Global Protection Parameters of the Inrush module
Parameter
Description
Setting range
Default
Menu path
ExBlo1
External blocking of the module, if blocking
is activated (allowed) within a parameter set
and if the state of the assigned signal is
true.
1..n,
Assignment List
-.-
[Protection
Para
/Global Prot
Para
/I-Prot
/IH2]
ExBlo2
External blocking of the module, if blocking
is activated (allowed) within a parameter set
and if the state of the assigned signal is
true.
1..n,
Assignment List
-.-
[Protection
Para
/Global Prot
Para
/I-Prot
/IH2]
Setting Group Parameters of the Inrush Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/IH2]
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/I-Prot
/IH2]
IH2 / IH1
Maximum permissible percentage of the 2nd
harmonic of the 1st harmonic.
10 - 40%
15%
[Protection
Para
/<1..4>
/I-Prot
/IH2]
450
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...