Service and Commissioning Support
Disarming the Relay Output Contacts
The parameters, their defaults, and setting ranges have to be taken from the
Relay Output Contacts section.
Principle – General Use
Within this mode [Service/Test Mode/DISARMED], entire groups of relay output contacts can be disabled.
By
means of this test mode, contact outputs switching actions of the relay output contacts are prevented.
If the relay
output contacts are disarmed, maintenance actions can be carried out without the risk of taking entire processes off-
line.
The User MUST ENSURE that the relay output contacts are ARMED AGAIN
after the maintenance is complete.
If they are not armed, the protective device
WILL NOT provide protection.
Zone Interlocking Output and the Supervision Contact cannot be disarmed.
Within this mode [Service/Test Mode/DISARMED] entire groups of relay output contacts can be disarmed:
Permanent; or
Via timeout.
If they are set with a timeout, they will only keep their “Disarm Position” as long as this timer runs. If the timer
expires, the relay output contacts will operate normally.
If they are set Permanent, they will keep the “Disarm State”
continuously.
A relay output contact will NOT be disarmed as long as:
It´s latched (and not yet reset).
As long as a running t-OFF-delay timer is not yet expired (hold time of a
relay output contact).
The Disarm Control is not set to active.
The Direct Command is not applied.
618
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...