Standards
Environmental Tests
Test Cab: Damp Heat (permanent)
IEC 60255 (6.12.3.6)
IEC 60068-2-78
Temperature
Relative humidity
test duration
60°C
95%
56 days
Test Nb:Temperature Change
IEC 60255 (6.12.3.5)
IEC 60068-2-14
Temperature
cycle
test duration
60°C/-20°C
5
1°C/5min
Test BD: Dry Heat Transport and storage test
IEC 60255 (6.12.3.3)
IEC 60068-2-2
Temperature
test duration
70°C
16 h
Test AB: Cold Transport and storage test
IEC 60255-1 (6.12.3.4)
IEC 60068-2-1
Temperature
test duration
-30°C
16 h