Blockings
Activate, Deactivate respectively Block Temporarily Protection Functions
(*) All protective elements will be blocked that are using fundamental or harmonics measured values, if the
frequency leaves the nominal frequency range. Protective elements that are using RMS values will remain active.
(**) This applies to devices that offer wide frequency range measurement only.
361
MRI4
DOK-HB-MRI4-2E
GeneralProt_Y03
Blockings
name .
ExBlo1
no assignment
1..n, Assignment List
&
Frequency is within the nominal frequency range.(*)(**)
1
name .
Function
inactive
active
name .
ExBlo Fc
inactive
active
name .
ExBlo2
no assignment
1..n, Assignment List
≥1
&
name . ExBlo
name . ExBlo1-I
name . ExBlo2-I
2
Please Refer To Diagram : Prot
Prot. active
(The General Protection module is not deactivated or blocked )
name . active
name = all modules that are blockable