 SSR530 and SSRL530 Series

1. Manufacturer  has  made  great  effort  on  product  quality  and  reliability,  but  improper

selection  or  use  may  result  in  irreversible  damage  of  internal  power  semiconductor
devices  in    solid  state  relay.  In  addition,  due  to  the  voltage  fluctuation  of  the  power  grid
(usually  +  +  +  10%)  and  the  differences  in  inductance  and  capacitance,  a  certain  safety
factor  must  be  taken  into  account  when  selecting  the  type.  For  example,  the  long-term
working current of electric heating should not exceed 60% of the rated SSR current, and
the rated current of the motor should not exceed 1/7 of ssr current.

2. When the long-term working current is greater than 5A, it must be equipped with the

supporting radiator. Radiator slab temperature shall not exceed 80 

.

If the ambient temperature is too high, air cooling must be adopted to accelerate air flow for
better cooling effect.

3. In order to ensure the closely contact of solid state relay with the radiator during the

installation process and to achieve more ideal cooling effect, our company equipped with
special thermal conductive film or special thermal conductive silicone according to the
different level of current.  When installing, please parallel the heat conduction film to the
solid state relay, between the bottom plate of the solid state relay and the radiator, and
install the mounting screws.

4. When the module is fastened to the surface of the radiator, it adopts M3, M4, M5 screws and

spring washers, and is fastened with 4-6nm torque. After 3 hours, it is fastened with the
same torque. Recommended tightening torque 0.8- 1 Nm for the controlling end M3 screw,
1.9 -2.1 Nm for loading end M5 screw.

5. In order to prevent the breakdown of solid state relay caused by short circuit, overload of

voltage or current, we strongly recommended installing relevant fast acting fuse (our
company can provide supporting services).

For the inductive load, it is also necessary to install the pressure-sensitive resistance and 
RC absorption circuit at the solid-state output end. For the dc solid-state relay, if it is the 
inductive load, it is necessary to install the relay diode protection. 

6. Solid state relays must operate with sufficient voltage and current values that do not exceed

the nominal trigger voltage and current value. For example, the control end is "3-32vdc", that