Protective Elements
IG> - Earth Fault [50N/G, 51N/G]
Available elements:
IG[1] ,IG[2] ,IG[3] ,IG[4]
If you are using inrush blockings the tripping delay of the earth current
protection functions must be at least 30 ms or more in order to prevent faulty
trippings.
All earth current elements are identically structured.
This module offers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
The following table shows the application options of the earth overcurrent protection element
Applications of the IE-Protection Module
Setting in
Option
ANSI 50N/G – Earth overcurrent protection,
non directional
Device Planning menu
Setting: non directional
Measuring Mode:
Fundamental/TrueRMS
ANSI 51N/G – Earth short circuit protection,
non directional
Device Planning menu
Setting: non directional
Measuring Mode:
Fundamental/TrueRMS
Measuring Mode
For all protection elements it can be determined, whether the measurement is done on basis of the »
Fundamental«
or if »
TrueRMS« measurement is used.
453
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...