Switchgear/Breaker – Manager
The protection device continuously supervises the status of the inputs
»Aux ON-I« and »Aux OFF-I«.
These signals are validated based on the supervision timers »
t-Move ON« and »t-Move OFF« validation functions.
As a result, the switchgear position will be detected by the following signals:
Pos ON
Pos OFF
Pos Indeterm
Pos Disturb.
Pos (State=0,1,.2 or 3)