Operating Panel (HMI)
Operating Panel (HMI)
HMI
Special Parameters of the Panel
This menu »Device Parameter/HMI« is used to define the contrast of the display, the maximum admissible edit time
and the menu language (after expiry of which, all unsaved parameter changes will be rejected).
Direct Commands of the Panel
Parameter
Description
Setting range
Default
Menu path
Contrast
Contrast
0 - 100%
50%
[Device Para
/HMI]
Reset Options
If the »C« key is pressed while the device is
performing a cold restart a general Reset
Dialog appears on the screen. Select which
options shall be available with this dialog.
Fact.def., "PW
rst",
Only
"Fact.defaults",
Reset deact.
Fact.def., "PW
rst"
[Device Para
/Security
/Miscellaneous]
Smart view via
USB
Activate (allow) or inactivate (disallow) the
Smart view access via the USB interface.
inactive,
active
active
[Device Para
/Security
/
Communication
]
Smart view via
Eth
Activate (allow) or inactivate (disallow) the
Smart view access via the Ethernet
interface.
inactive,
active
active
[Device Para
/Security
/
Communication
]
Global Protection Parameters of the Panel
Parameter
Description
Setting range
Default
Menu path
t-max
Edit/Access
If no other key(s) is pressed at the panel,
after expiration of this time, all cached
(changed) parameters are canceled. The
device access will be locked by falling back
into Read-only level Lv0.
20 - 3600s
180s
[Device Para
/Security
/Miscellaneous]
163
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...