Blockings
Current protective functions cannot only be blocked permanently (
»
function = inactive«) or temporarily by any
blocking signal from the »assignment list«, but also by
»reverse Interlocking«.
All other protection functions can be activated, deactivated or blocked in the same manner.
(*) All protective elements will be blocked that are using fundamental or harmonics measured values, if the
frequency leaves the nominal frequency range. Protective elements that are using RMS values will remain active.
(**) This applies to devices that offer wide frequency range measurement only.
362
MRI4
DOK-HB-MRI4-2E
Blockings (**)
Pdoc_Y05
I/IG .
ExBlo1
no assignment
1..n, Assignment List
&
Frequency is within the nominal frequency range.(*)(**)
1
I/IG .
Function
inactive
active
I/IG .
ExBlo Fc
inactive
active
I/IG .
ExBlo2
no assignment
1..n, Assignment List
≥1
&
I/IG . ExBlo
I/IG . ExBlo1-I
I/IG . ExBlo2-I
4
Please Refer To Diagram: Prot
Prot. active
(The General Protection module is not deactivated or blocked)
I/IG . active
I/IG = I[1]...[n], IG[1]...[n]
I/IG .
Ex rev Interl
no assignment
1..n, Assignment List
I/IG .
Ex rev Interl Fc
inactive
active
&
I/IG . Ex rev Interl
I/IG . Ex rev Interl-I
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...