Protective Elements
Protective Elements
I - Overcurrent Protection [50, 51,51Q, 51V*]
Available stages:
I[1] ,I[2] ,I[3] ,I[4] ,I[5] ,I[6]
If you are using inrush blockings the tripping delay of the current protection
functions must be at least 30ms or more in order to prevent faulty trippings.
All overcurrent protective elements are identically structured.
This module offers Adaptive Parameter Sets.
Parameters can be modified within parameter sets dynamically by means of
Adaptive Parameter Sets.
Please refer to chapter Parameter / Adaptive Parameter Sets.
The following table shows the application options of the Overcurrent Protection element
Applications of the I-Protection Module
Setting in
Option
ANSI 50 – Overcurrent protection, non-
directional
Device Planning menu
Measuring Mode:
Fundamental/TrueRMS/negative
phase sequence current (I2)
ANSI 51 – Short circuit protection, non-
directional
Device Planning menu
Measuring Mode:
Fundamental/TrueRMS/negative
phase sequence current (I2)
ANSI 51V – Voltage restraint overcurrent
protection
*
Parameter Set:
VRestraint = active
Measuring Mode:
Fundamental/TrueRMS/negative
phase sequence current (I2)
Measuring Channel:
Phase to Phase/Phase to Neutral
ANSI 51Q Negative Phase Sequence
Overcurrent Protection
Parameter Set:
Measuring Method =I2
(Negative Sequence
Current)
51C Voltage controlled overcurrent
protection
*
(Please refer to the chapter
Parameter/Adaptive Parameter)
Adaptive Parameters
Measuring Mode:
Fundamental/TrueRMS/negative
phase sequence current (I2)
Measuring Channel:
(in voltage protection module)
Phase to Phase/Phase to Neutral
*
=available only for devices that offer voltage measurement.
416
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...