Protective Elements
Direct Commands of the Automatic Reclosure Module
Parameter
Description
Setting range
Default
Menu path
Res TotNo suc
unsuc
Reset all statistic AR counters: Total number
of AR, successful and unsuccessful no of AR.
inactive,
active
inactive
[Operation
/Reset]
Res Service Cr
Reset the Service Counters
inactive,
active
inactive
[Operation
/Reset]
Reset Lock via
HMI
Reset the AR Lockout via the panel.
inactive,
active
inactive
[Operation
/Reset]
Res Max Shots /
h Cr
Resetting the Counter for the maximum
allowed shots per hour.
inactive,
active
inactive
[Operation
/Reset]
Device Planning Parameters of the Module Automatic Reclosure
Parameter
Description
Options
Default
Menu path
Mode
Mode
do not use,
use
do not use
[Device planning]
527
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...