Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Master Id
MasterId defines the DNP3 address of
master (SCADA)
0 - 65519
65500
[Device Para
/DNP3
/
Communication
]
Global Protection Parameters of the DNP
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[Device Para
/DNP3
/
Communication
]
IP Port Number IP Port Number.
In general it is recommended to keep the
default value. if this is not possible then
select a number out of the private range
49152-52151 or 52162-65535 that is not
yet in use within your network.
0 - 65535
20000
[Device Para
/DNP3
/
Communication
]
Baud rate
Baud rate for communication
1200,
2400,
4800,
9600,
19200,
38400,
57600,
115200
19200
[Device Para
/DNP3
/
Communication
]
Frame Layout
Frame Layout
8E1,
8O1,
8N1,
8N2
8E1
[Device Para
/DNP3
/
Communication
]
Optical rest
position
Optical rest position
Light off,
Light on
Light on
[Device Para
/DNP3
/
Communication
]
253
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...