Communication Protocols
Modbus TCP
Establishing a connection via TCP/IP to the device is only possible if your
device is equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: Setting the TCP/IP Parameters
Call up
»Device parameter/TCP/IP« at the HMI (panel) and set the following parameters:
TCP/IP address
Subnetmask
Gateway
Part 2: Configuration of the Devices
Call up
»Device parameter/Modbus« and set the following communication parameters:
Setting a Unit Identifier is only necessary if a TCP network should be coupled to a RTU network.
If a different port than the default port 502 should be used please proceed as follows:
Choose “Private” within the TCP-Port-Configuration.
Set the port-number.
Set the maximum accepted time of “no communication”. If this time has expired – without any comunication,
the device concludes a failure within the master system.
Allow or disallow the blocking of SCADA commands.
Part 3: Hardware Connection
There is a RJ45 interface at the rear side of the device for the hardware connection to the control system.
Establish the connection to the device by means of a proper Ethernet cable.
Direct Commands of the Modbus
®
Parameter
Description
Setting range
Default
Menu path
Res Diagn Cr
All Modbus Diagnosis Counters will be reset. inactive,
active
inactive
[Operation
/Reset]
192
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...