Technical Data
Voltage Supply
Aux. Voltage:
24V - 270 V DC/48 - 230 V AC (-20/+10%)
≂
Buffer time in case of supply failure:
>= 50 ms at minimal aux. voltage. The device will shut down if
the buffer time is expired
Note: communication could be interrupted
Max. permissible making current:
18 A peak value for
0.25 ms
12 A peak value for
1 ms
The voltage supply must be protected by a fuse of:
2,5 A time-lag miniature fuse 5x20 mm (approx. 1/5” x 0.8”) according to IEC 60127
3,5 A time-lag miniature fuse 6,3x32 mm (approx. 1/4” x 1 1/4”) according to UL 248-14
Power Consumption
Power supply range:
Power consumption
in idle mode
Max. power consumption
24-270 V DC:
7 W
10 W
48-230 V AC
(for frequencies of 50-60 Hz):
7 W / 13 VA
10 W / 17 VA
631
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...