Protective Elements
Set Parameters of the Cold Load Pickup Module
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of
module/stage.
inactive,
active
inactive
[Protection
Para
/<1..4>
/CLPU]
ExBlo Fc
Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "ExBlo Fc=active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/CLPU]
Ex rev Interl Fc Activate (allow) or inactivate (disallow)
blocking of the module/stage. This
parameter is only effective if a signal is
assigned to the corresponding global
protection parameter. If the signal becomes
true, those modules/stages are blocked that
are parameterized "Ex rev Interl Fc =
active".
inactive,
active
inactive
[Protection
Para
/<1..4>
/CLPU]
t-Load Off
Select the outage time required for a load to
be considered cold. If the Pickup Timer
(Delay) has run out, a Cold Load Signal will
be issued.
0.00 - 7200.00s 1.00s
[Protection
Para
/<1..4>
/CLPU]
t-Max Block
Select the amount of time for the cold load
inrush. If the Release Time (Delay) has run
out, a Warm Load Signal will be issued.
0.00 - 300.00s
1.00s
[Protection
Para
/<1..4>
/CLPU]
I<
The CB is in the OFF Position, if the
measured current is less than this
parameter.
0.01 - 1.00In
0.01In
[Protection
Para
/<1..4>
/CLPU]
Threshold
Set the load current inrush threshold.
0.10 - 4.00In
1.2In
[Protection
Para
/<1..4>
/CLPU]
Settle Time
Select the time for the cold load inrush
0.00 - 300.00s
1.00s
[Protection
Para
/<1..4>
/CLPU]
508
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...