Switchgear/Breaker – Manager
Trip Manager – Assignment of commands
The trip commands of the protection elements have to be assigned within menu [Control/Bkr/Trip Manager] to the
switchgear (presumed, that the switchgear is make/break capable) .
In the Trip Manger all tripping commands are combined by an “OR” logic. The actual tripping command to the
switchgear is exclusively given by the Trip Manager
. This means, that only tripping commands which are assigned
in the Trip Manager lead to an operation of the switchgear.
In addition to that, the User can set the minimum hold
time of the tripping command within this module and define whether the tripping command is latched or not.
381
MRI4
DOK-HB-MRI4-2E
Aux ON-I
Aux OFF-I
Ready-I
SG[x].OFF Cmd1
SG[x].OFF Cmd2
SG[x].OFF Cmd3
S
G
[x
]
OFF Cmd
ON Cmd
TripCmd
Prot ON
I[1].TripCmd
I[2].TripCmd
I[3].TripCmd
I
P
ro
te
ct
io
n
M
o
d
u
le
V[1].TripCmd
V[2].TripCmd
V[3].TripCmd
V
P
ro
te
ct
io
n
M
o
du
le
HMI
Autoreclosure CLOSE
Command
Scada
* Availability dependent on
device type
*
*
A
va
ila
b
ili
ty
d
ep
en
de
nt
o
n
de
vi
ce
t
yp
e
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...