REU 523

Combined overvoltage and undervoltage 
relay

Features

• Over and undervoltage protection

• Single- or three-phase use

• High-set overvoltage stage with definite-

time or inverse definite minimum time 
(IDMT) characteristic

• Low-set overvoltage stage with definite-

time or IDMT characteristic

• High-set undervoltage stage with definite-

time or IDMT characteristic

• Low-set undervoltage stage with definite-

time or IDMT characteristic

• Positive-phase-sequence protection

• Adjustable drop-off/pick-up ratio for the 

low-set stages

• Circuit-breaker failure protection (CBFP)

• Disturbance recording up to 12 seconds

-

triggering by a start or a trip signal from 
any protection stage and/or by a binary 
input signal

-

records three analogue channels and 
eight digital channels

-

adjustable sampling rate

• Non-volatile memory for

-

up to 60 event codes

-

setting values

-

disturbance recorder data

-

recorded data of the five last events with 
time stamp

-

number of starts for each stage

- alarm indication messages and LEDs 

showing the status at the moment of 
power failure

• Three accurate voltage inputs

• Galvanically isolated binary input with a 

wide input voltage range

• All settings can be modified with a personal 

computer

• HMI with an alphanumeric LCD and 

manoeuvring buttons

• IEC 60870-5-103 and SPA bus communi-

cation protocols

• Two normally open power output contacts

• Two change-over signal output contacts

• Output contact functions freely configura-

ble for desired operation

• Optical PC-connector for two-way data 

communication (front)

• RS-485 connector (rear) for system com-

munication

• Continuous self-supervision of electronics 

and software. At an internal relay fault, all 
stages and outputs are blocked

• User-selectable rated frequency 50/60 Hz

• User-selectable nominal voltage 100/110/ 

115/120 V

• User-selectable password protection for 

the HMI

• Display of primary voltage values

• Demand values

• Multi-language support

Summary of Contents for REU 523

Page 1: ...volatile memory for up to 60 event codes setting values disturbance recorder data recorded data of the five last events with time stamp number of starts for each stage alarm indication messages and L...

Page 2: ...ate time at definite time characteristic or the calcu lated operate time at IDMT characteristic elapses the overvoltage unit will deliver a trip signal The low set and the high set stage of the overvo...

Page 3: ...ies according to the selected sampling frequency The RMS curve is recorded by selecting the sampling fre quency to be the same as the nominal fre quency of the relay See the table below for details HM...

Page 4: ...l is used to connect the relay to the CAP 501 505 setting and configuration tools The front interface uses the SPA bus protocol The opti cal PC connector galvanically isolates the PC from the relay Si...

Page 5: ...e constant L R 40 ms at 48 110 220 V dc 5 A 3 A 1 A Minimum contact load 100 mA at 24 V ac dc 7DEOH 6LJQDO RXWSXWV 62 62 DQG VHOI VXSHUYLVLRQ RXWSXW 5 Rated voltage 250 V ac dc Continuous carry 5 A Ma...

Page 6: ...68 2 2 Dry cold test according to the IEC 60068 2 1 Damp heat test cyclic according to the IEC 60068 2 30 7DEOH 6WDQGDUG WHVWV QVXODWLRQ WHVWV Dielectric tests According to the IEC 60255 5 Test voltag...

Page 7: ...disturbance tests According to the IEC 60255 22 4 and IEC 61000 4 4 Other terminals 4 kV Binary input 2 kV Surge immunity test According to the IEC 61000 4 5 Power supply 4 kV line to earth 2 kV line...

Page 8: ...SGB1 SGB1 SGB1 X 3 X 3 2 X 2 X 1 X 1 X X 4 X 4 5 6 3 4 13 14 15 1 2 17 18 1 3 4 6 7 9 SGB1 SGB1 5 6 10 11 12 7 8 9 X2 1 X1 1 100 V 110 V 115 V 3U 3U SGB1 7 SGB1 8 X 4 X 4 X 3 X 3 2 X 2 X 1 X 1 X 3U 3U...

Page 9: ...ined Overvoltage and Undervoltage relay Hardware number KHQ RUGHULQJ SOHDVH VSHFLI Ordering information Ordering example 1 Type designation and quantity REU 523 5 pieces 2 Order number REU523B 409 BAA...

Page 10: ...ABB Oy P O Box 699 FIN 65101 Vaasa Finland Tel 358 10 224 000 Fax 358 10 224 1094 www abb com substationautomation...