INSTALLATION AND SERVICE INSTRUCTION

Siemens
Energy & Automation

 

 
 

SD66 

 

Rev 11 

 

January 2006 

 

Supersedes Rev 10 

 

Model Series 66 Amplifying and Reducing Relays 

 

INTRODUCTION 

 
The Model Series 66 Amplifying and Reducing Relays are used in control circuit to amplify and reduce pneumatic 
signals. The output of a relay is proportional to its input by the fixed gain factor of that relay model. 
 
This instruction has six major sections: Introduction, Installation, Principle of Operation, Maintenance, Warranty, 
and Parts List. 
 

Model Designation 

 

 

 

 

 

66 

BA 

Model Series 

Material and Function 
 

A – Brass, Amplifying 

 

R – Brass, Reducing 

Input-to-Output Ratio 

2 - 

1:2, Model 66BA2 

2:1, Model 66BR2 

4 - 

1:4, Model 66BA4 

4:1, Model 66BR4 

3 - 

1:3, Model 66BA3 

3:1, Model 66BR3 

6 - 

1:6, Model 66BA6 

6:1, Model 66BR6 

 

Specifications 

 
Supply Pressure 
 Normal..................................... 20 

psig 

 Minimum................................. 1 

psig 

above maximum required output 

 Maximum ................................ 80 

psig 

Normal Operating Range....................... 3 to 15 psig 
Operating Range Limits 
 

Amplifying Relay .................... Not to exceed 80 psig output 

 

Reducing Relay ....................... Not to exceed 80 psig input 

Overrange Limits................................... 100 psig to any connection 
Ambient Temperature Limits ................ -40° to +180°F (-40° to +82°C) 
 

StockCheck.com

Summary of Contents for 66 Series

Page 1: ...eration Maintenance Warranty and Parts List Model Designation 66 BA 2 Model Series Material and Function A Brass Amplifying R Brass Reducing Input to Output Ratio 2 1 2 Model 66BA2 2 1 Model 66BR2 4 1 4 Model 66BA4 4 1 Model 66BR4 3 1 3 Model 66BA3 3 1 Model 66BR3 6 1 6 Model 66BA6 6 1 Model 66BR6 Specifications Supply Pressure Normal 20 psig Minimum 1 psig above maximum required output Maximum 80...

Page 2: ...may cause damage to the relay Pressures in excess of those stated in the Specifications section may cause damage to the relay Instrument Air Requirements Connect the instrument i e relay to a source of clean dry oil free instrument air Failure to do so will increase the possibility of a malfunction or a deviation from specified performance CAUTION Use of process fluids other than instrument air is...

Page 3: ...ive areas of the input diaphragm and output diaphragm assembly The input diaphragm of an Amplifying Relay has a larger effective area than the output diaphragm assembly which requires the output to be proportionally higher for the relay to be in balance see Figure 2 Amplifying View Conversely the input diaphragm of a Reducing Relay has a smaller effective area than the output diaphragm assembly wh...

Page 4: ... port Supply port is clogged due to build up on the plunger and or supply port Refer to Maintenance Cleaning and clean plunger and supply port Output pressure will not increase or increases with an increase in input pressure Supply pressure is too low Raise supply pressure Ruptured input diaphragm or output diaphragm assembly Refer to Maintenance to replace input diaphragm or output diaphragm asse...

Page 5: ...d plunger spring 7 Insert a 1 16 Allen wrench through the exhaust port in the bottom forging make adjustment 8 Install plunger plunger spring and retaining nut 9 Repeat steps 4 through 8 until span is set Function and Ratio Change The function and or ratio of a Relay can be changed using standard parts To change the function from amplifying to reducing or vice versa with the same ratio e g Model 6...

Page 6: ...formation is provided on the product nameplate part number or model number serial number and or version For most software this information is given in the Help About screen If there is a problem with product operation Is the problem intermittent or repeatable What symptoms have been observed What steps configuration changes loop modifications etc were performed before the problem occurred What sta...

Page 7: ...t the goods do not conform to the above warranty Repaired and replacement parts shall be warranted for the remainder of the original period of notification set forth above but in no event less than 12 months from repair or replacement At its expense Buyer shall remove and ship to Seller any such nonconforming items and shall reinstall the repaired or replaced parts Buyer shall grant Seller access ...

Page 8: ...is subject to change without notice Procedures in this document have been reviewed for compliance with applicable approval agency requirements and are considered sound practice Neither Siemens Energy Automation Inc nor these agencies are responsible for repairs made by the user IMPORTANT Service Parts Kits are available for servicing the instrument Contact Siemens for available kits refer to the P...

Reviews: