Protective Elements
Parameter
Description
Setting range
Default
Menu path
t-DE4
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 4-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl4]
t-DE5
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 5-6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl5]
t-DE6
Dead time between trip and reclosure
attempt for earth faults
Only available if: Shots = 6
0.01 - 9999.00s 1s
[Protection
Para
/<1..4>
/AR
/Shot Manager
/Shot Ctrl6]
t-Blo after CB
man ON
This timer will be started if the circuit
breaker was switched on manually. While
this timer is running, AR cannot be started.
0.01 - 9999.00s 10.0s
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-Lock2Ready
This timer is started by the lockout reset
signal, and before the timer expire the AR
cannot go to any other state.
0.01 - 9999.00s 10.0s
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-Run2Ready
Examination Time: If the Circuit Breaker
remains after an reclosure attempt for the
duration of this timer in the Closed position,
the AR has been successful and the AR
module returns into the ready state.
0.01 - 9999.00s 10.0s
[Protection
Para
/<1..4>
/AR
/General
Settings]
t-Blo2Ready
The release (de-blocking) of the AR will be
delayed for this time, if there is no blocking
signal anymore.
0.01 - 9999.00s 10.0s
[Protection
Para
/<1..4>
/AR
/General
Settings]
533
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...