Service and Commissioning Support
Forcing Analog Inputs*
* = Availability depends on ordered device.
The parameters, their defaults, and setting ranges have to be taken from
Analog Inputs section.
Principle – General Use
The User MUST ENSURE that the Analog Inputs operate normally after
maintenance is completed.
For commissioning purposes or for maintenance, Analog Inputs can be set by force.
Within this mode [Service/Test Mode (Prot inhibit)/WARNING! Cont?/Analog Inputs], Analog Inputs can be set by
force:
Permanent; or
Via timeout.
If they are set with a timeout, they will only keep their “Forced Value” as long as this timer runs.
If the timer
expires,
the Analog Input will operate normally.
If they are set as »
Permanent«, they will keep the “Forced Value”
continuously. This menu will show the current value that is fed to the Analog Input until the User activates the force
mode by calling up the »
Function«. As soon as the force mode is activated, the shown value will be frozen as long
as this mode is active. Now the User can force the Analog Input value. As soon as the force mode is deactivated,
measured value will be shown again.
622
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...