Supervision
Self Supervision within the devices
Parameter Setting (Device)
Protecting the parameter setting by
plausibility checks.
Implausibilities within the parameter
configuration can be detected by
means of plausibility checks.
Detected implausibilities are
highlighted by a question mark
symbol. Please refer to chapter
parameter setting for detailed
information.
Quality of the power supply
A hardware circuit ensures that the
device can only be used, if the power
supply is in the range specified by
the technical data.
If the supply voltage is too low, the
device will not start up or it will be set
out of service respectively.
Sags of the supply voltage
Short-term sags of the supply
voltage are detected and can be
bridged in most of the cases by
means of the integrated buffer within
the power supply hardware.
This buffer also allows the
termination of ongoing data writing
procedures.
The module for the supervision of the
system utilization will detect
repetitive short-term sags of the
supply voltage.
Internal data of the device
(memory load, internal resources, ...)
An internal module monitors the
system utilization.
The module for the supervision of the
system utilization initiates in case of
a fatal error a reboot of the device. In
case of minor faults the System LED
will flash alternating red and green
(please refer to the
Troubleshooting
Guide). The issue will be recorded as
a system message.
Battery
The battery is monitored
continuously.
Notice: The battery serves as buffering of the
clock (real time clock). There's no impact on
the functionality of the device if the battery
breaks down, except for the buffering of the
clock while the unit is in de-energized
condition.
If the battery is low the System LED
will flash alternating red and green
(please refer to the
Troubleshooting
Guide).
Status of the device communication
(SCADA)
The projected and activated SCADA
module supervises its connection to
the master communication system.
You can check if there is active
communication with the master
system within menu <Operation/
Status display/ Communication>.
In order to monitor this state you can
assign this status onto an LED
and/or an output relay.
For details on the status of the
GOOSE communication please refer
to chapter IEC61850.
598
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...