Short Operating Manual UFR1001E

   

   updated:120522WL/Fz

  

- NA-protection according to VDE-AR-N 4105, power generators at the low voltage grid
- for use in power generators at the medium voltage grid according to BDEW
- with selectable vector shift detection

Operating controls 

Test button 

Press 
shortly 

Output relays de-energize immediately. If Y1+Y2 are connected and the feedback 
signal is activated, the tripping time is displayed as long as no button is actuated

 

LEDs Frequency / voltage, above / below threshold 

(red)

 

ON, 

8

AL  

8

or 

8

AL M

8

Above / below threshold 

Flashing, 

8

AL 

88

or 

8

AL M

8

OFF-delay 

8

dof 

8

  active 

LED Vektor shift 

(VSR, red)

 

ON, 

8

AL 

8

 

Threshold value for vector shift exceeded 

Flashing, 

8

AL 

8

 

OFF-delay 

8

dof 

8

  active 

LEDs  Relay status 

(yellow)

 

OFF 

Relays de-energized 

ON 

Relays energized 

Digital display 4-digit 

(red)

 

Depending on program, display of current voltage, frequency, vector shift, average value 
Display of alarm message 

8

AL  

8

8

aL M

8

 

Display of error with error code e.g.  

8

Err9

8

 

LED Time 

(yellow)

 

ON 

A time is displayed 

Backmost decimal point 

(red)

 

OFF 

Display mode 

Lightning 

Menu mode 

Flashing 

Configuration mode 

Set / Reset button   

(in display mode, normal state)

 

Press shortly 

Display of next measured value / alarm counter 

Press for > 2 s 

Reset, quit error messages 

Press for > 4 s 

Display of program, e.g. 

8

Pr 1

8

 

Press for > 10 s 

Display of firmware version, e.g. 

8

0-01

8

 

Temperature-Relays, Grid-Relays, Digital Panelmeters MINIPAN, Switching Relays and Controls, Transducers 

ZIEHL  industrie 

– elektronik  GmbH  + Co  KG 

Daimlerstraße 13, D 

– 74523  Schwäbisch Hall 

+ 49 791 504-0,   [email protected],  www.ziehl.de

- Archive document -

Summary of Contents for UFR1001E

Page 1: ...ceeded Flashing 8AL 8 OFF delay 8dof 8 active 4 LEDs Relay status yellow OFF Relays de energized ON Relays energized 5 Digital display 4 digit red Depending on program display of current voltage frequ...

Page 2: ...imulation enabled Description of the connections A1 and A2 Rated control supply voltage Us see Technical Data any polarity 11 12 14 21 22 24 Relay K1 and K2 E1 E2 Enable input needed only for vector s...

Page 3: ...ent clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or interference with the cooling air current the permis...

Page 4: ...button 5x Display 8Pr 1 8 Set the program with the buttons Press button 1x Display 8 no 8 Press button 1x Display 8 yes 8 Press button Device resets and starts with the newly selected program Hint Wh...

Page 5: ...s Up Down simultaneously sets the values to the smallest one Code Reset Press button Set 2 s while applying control supply voltage Pin 504 Error reports Err4 Tolerance Master Slave Err5 internal regul...

Page 6: ...Overvoltage V 253 438 253 438 253 438 HM Hysteresis V 3 0 3 0 3 0 3 0 3 0 3 0 dal ON delay s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 60 60 60 U_ u_ Alarm on off on on On On on on u_ Un...

Page 7: ...h rEL trEL Switching time Y1 Y2 s 5 0 5 0 off off off off ddi ddi Display delay s 0 5 0 5 0 5 0 5 0 5 0 5 dit Display duration SCn s 3 5 3 5 3 5 3 5 3 5 3 5 Si U Voltage V 230 400 57 7 100 230 400 F F...

Page 8: ...r88 appears in the display Hysteresis error overlapping of the release points Upper threshold value must be higher than the lower threshold value check the threshold values 8Err98 appears in the displ...

Reviews: