ZIEHL UFR1001E Short Operating Manual Download Page 2

 

UFR1001E 

12420-0751-00

  

Page

 

2 / 8 

 www.ziehl.de 

 

Up / Down button 

 

(in display mode, normal state)

 

 

Press shortly 

Change to the menu mode, display of alarm memory (Down) / 
cumulative time of alarms (Up), additional pushing of Set button for 

≥ 2 s 

makes a reset of the stored values  

 

Press for > 2 s 

Display of MAX (Up) / MIN (Down) measured values, additional pushing 
of Set button for 

≥ 2 s deletes the stored values 

10  LEDs Allocation of the measured value 

(yellow)

 

 

LEDs 

Measured value 

 

Lx and N ON 

Voltage (L1 against N, L2 against N, L3 against N) 

Lx and Ly ON 

Voltage (L1 against L2, L2 against L3, L1 against L3) 

Lx flashing quickly 

Vector shift (L1, L2, L3) 

L1 flashing 

Frequency 

11 

Sealable  LED 

 

  

Press for > 2 s 

Lock / Unlock 

 

 LED  red 

Settings and simulation mode are locked, 
in case of setting attempts 

8

LOc 

8

 is displayed for 3 s 

 

 LED green 

Setting and simulation enabled 

 

Description of the connections 

A1 and A2  

Rated control supply voltage U

s

, see Technical Data  (any polarity) 

11, 12, 14; 21, 22, 24

 

Relay K1 and K2

 

E1 

– E2  

Enable-input, needed only 
for vector shift detection 

Volt-free n/c contact 

Contact closed, no evaluation of vector shift (suppression) 

Contact open, evaluation of vector shift 

Y0, Y1, Y2 
Inputs, feedback contacts 

Volt-free n/o or n/c contact, self-learning when switching on 

Adjust the turn-on time of the section switch under  

8

trel.

8

 / switch-off 

if not used  

I1 

Supply voltage for digital outputs, max. 27 V DC 

Q1…Q4 

Digital output over-/undervoltage/-frequency 

Q5 

Digital output Error, in Pr 3 + 4 additionally the 2nd threshold value 

L1, L2, L3, N 

Phase L1, L2, L3 and neutral conductor 

 

Important notice 

  

In the supply line in the vicinity of the device (easily accessible), a switch marked 

 

as disconnecting device as well as an overcurrent protection element (rated current 

 

≤ 6 A) have to be provided.  

 

 

   

 

  Attention! 

 

  For the rated control supply voltage, see label at the side of the unit!  

 
 

 

!

!

Summary of Contents for UFR1001E

Page 1: ...ceeded Flashing 8AL 8 OFF delay 8dof 8 active 4 LEDs Relay status yellow OFF Relays de energized ON Relays energized 5 Digital display 4 digit red Depending on program display of current voltage frequ...

Page 2: ...imulation enabled Description of the connections A1 and A2 Rated control supply voltage Us see Technical Data any polarity 11 12 14 21 22 24 Relay K1 and K2 E1 E2 Enable input needed only for vector s...

Page 3: ...ent clearance to other devices or heat sources If cooling is inhibited e g through close proximity to devices with increased surface temperature or interference with the cooling air current the permis...

Page 4: ...button 5x Display 8Pr 1 8 Set the program with the buttons Press button 1x Display 8 no 8 Press button 1x Display 8 yes 8 Press button Device resets and starts with the newly selected program Hint Wh...

Page 5: ...s Up Down simultaneously sets the values to the smallest one Code Reset Press button Set 2 s while applying control supply voltage Pin 504 Error reports Err4 Tolerance Master Slave Err5 internal regul...

Page 6: ...Overvoltage V 253 438 253 438 253 438 HM Hysteresis V 3 0 3 0 3 0 3 0 3 0 3 0 dal ON delay s 0 10 0 10 0 10 0 10 0 10 0 10 dof OFF delay s 60 60 60 60 60 60 U_ u_ Alarm on off on on On On on on u_ Un...

Page 7: ...h rEL trEL Switching time Y1 Y2 s 5 0 5 0 off off off off ddi ddi Display delay s 0 5 0 5 0 5 0 5 0 5 0 5 dit Display duration SCn s 3 5 3 5 3 5 3 5 3 5 3 5 Si U Voltage V 230 400 57 7 100 230 400 F F...

Page 8: ...r88 appears in the display Hysteresis error overlapping of the release points Upper threshold value must be higher than the lower threshold value check the threshold values 8Err98 appears in the displ...