Protective Elements
Parameter
Description
Setting range
Default
Menu path
Char
Characteristic
DEFT,
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
RINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T,
RXIDG
DEFT
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
t
Tripping delay
Only available if: Characteristic = DEFT
0.00 - 300.00s
0.00s
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
tchar
Time multiplier/tripping characteristic factor.
The setting range depends on the selected
tripping curve.
Only available if: Characteristic = INV Or
Characteristic = Therm Flat Or
Characteristic = IT Or Characteristic = I2T
Or Characteristic = I4TOr Characteristic =
RXIDG
0.02 - 20.00
1
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
Reset Mode
Reset Mode
Only available if: Characteristic = INV Or
Characteristic = Therm Flat Or
Characteristic = IT Or Characteristic = I2T
Or Characteristic = I4TOr Characteristic =
RXIDG
instantaneous,
delayed,
calculated
instantaneous [Protection
Para
/<1..4>
/I-Prot
/IG[1]]
t-reset delay
Reset delay for intermittent phase failures
(INV characteristics only)
Only available if: Characteristic = INV Or
Characteristic = Therm Flat Or
Characteristic = IT Or Characteristic = I2T
Or Characteristic = I4TOr Characteristic =
RXIDG Only available if:Reset Mode =
delayed
0.00 - 60.00s
0.00s
[Protection
Para
/<1..4>
/I-Prot
/IG[1]]
474
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...