Communication Protocols
Parameter
Description
Setting range
Default
Menu path
Scale Factor 18 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 18
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
19
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
Scale Factor 19 The scale factor is used to convert the
measured value in an integer format
0.001,
0.01,
0.1,
1,
10,
100,
1000,
10000,
100000,
1000000
1
[Device Para
/DNP3
/Point map
/Analog Input]
Dead Band 19
If a change of measured value is greater
than the deadband value it will be reported
to the master.
0.01 - 100.00% 1%
[Device Para
/DNP3
/Point map
/Analog Input]
Analog value
20
Analog value can be used to report values
to the master (DNP)
1..n,
TrendRecList
-.-
[Device Para
/DNP3
/Point map
/Analog Input]
274
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...