Description

Specifi cations

The  fi re  detection  control  panels  Series  BC216  and 

BC016, respectively, provide 16 freely programmable 

open-collector control outputs. Eight of these outputs 

are connected to a fl at cable connector. The Relay Mo-

dules RL58-1 and RL58-2 allow for the easy conversion 

of these control outputs to dry changeover contacts. 

The componentry is connected to the fi re detection con-

trol panel via a fl at cable.

The RL58-1 provides eight relay outputs with a maxi-

mum contact rating of 30W. The current is limited to 1A 

and the voltage is limited to 60VDC. The RL58-2 offers 

four relay outputs with a maximum of 5A/230VAC. The 

terminal of the RL58-2 are designed for mains voltage. 

Two relay modules RL58-2 are each cascadable via pin 

connectors. The relay module is delivered with fl at ca-

ble and mounting accessories for easy installation.

•   8 or 4 relay outputs, respectively, 

with one dry changeover contact 

each

•   Actuation display by LED for each 

output

•  Switch contacts on terminals
•   Easy mounting on componentry 

carrier

•   Connection with control panel via fl at 

cable

Operating voltage 

20 – 31VDC

Current consumption at 24V 

typ. 22mA per activated circuit

Control current 

typ. 1.2mA per input

Ambient temperature 

-5°C to +50°C

RL58-1

Switching power per contact 

1A/60V/30W

Contact life 

 approx. 5 mill. switching cycles (unloaded)

approx. 300,000 switching cycles (at 24VDC/1A)

Dimensions L × W × H 

85 × 65 × 37 (mm)

Weight 

330g

Part No. 

222004

Order name 

Relay Module 8-Fold/60VDC RL58-1