background image

ABB Automation Inc.

Substation Automation and Protection Division
Coral Springs, FL 33065

Instruction Leaflet

All possible contingencies which may arise during installation, operation or maintenance, and all
details and variations of this equipment do not purport to be covered by these instructions. If further
information is desired by purchaser regarding this particular installation, operation or maintenance
of this equipment, the local ABB Power T&D Company Inc. representative should be contacted.

Printed in U.S.A

.

!

CAUTION

Before putting relays into service, remove all

blocking which may have been inserted for the

purpose of securing the parts during shipment,

make sure that all moving parts operate freely,

inspect the contacts to see that they are clean

and close properly, and operate the relay to

check the settings and electrical connections.

1.0

APPLICATION

The type CM relay is an induction type relay designed
to protect polyphase electrical machinery against
phase unbalance or phase failure.

As shown in figure 6 the relay may be used with
either three or two-current transformers. With three
ct’s the accuracy class must be at least C50; with two
ct’s the accuracy class must be at least C70. Other-
wise ct errors during motor starting may cause
undesired CM tripping.

2.0

CONSTRUCTION & OPERATION

The type CM relay consists of two main current units
and their associated resistor and an indicating con-
tactor switch (ICS), or an ac indicating contactor
switch (ACS). The principal component parts of the
relay and their location are shown in figures 1 and 2.

2.1. MAIN UNIT

Each main unit has a pair of electromagnets operat-

ing on a single disc. The disc is damped by a perma-
nent magnet. Each disc carries its own set of
contacts with the two sets being connected in paral-
lel, in order that either disc may close the trip circuit.
The electromagnet pair are mounted face to face on
opposite sides of the disc, and so connected that the
electrical torque of one electromagnet opposes that
of the other, thus producing balanced operating
torque on the disc when the magnitudes of the cur-
rents through each of the two electromagnets are
equal. One of the electromagnets on the lower disc is
connected in series with one of the electromagnets
on the upper disc. Thus phase A current may balance
phase B current on the upper disc, and phase B cur-
rent balance C current on the lower disc. Conse-
quently with balanced system conditions, no
operating torque is produced on the two discs, but
with unbalanced conditions or an open phase the bal-
ance on the disc is upset and one or two sets of con-
tacts close.

Each electromagnet has a main coil located on the
center leg of an “E” type laminated structure that pro-
duces a flux which divides and returns through the
outer legs. A shading coil located on one of the outer
legs of the “E” structure causes the flux through that
leg to lag the main pole flux. The out-of-phase fluxes
thus produced in the air gap will cause disc rotation.
A resistor located to the rear of each main unit is
used as an aid in balancing the opposing torques by
controlling the current flow through the shading coils.

For some CM relays, the front electromagnet may
have adjustable plugs which are used to aid in cali-
bration.

41-181.2K

Effective:

June 1980

Supersedes I.L.  41-181.2J, dated March 1978

( | ) Denotes Change Since Previous Issue

Type CM Phase
Balance Current Relay

Summary of Contents for CM

Page 1: ...has a pair of electromagnets operat ing on a single disc The disc is damped by a perma nent magnet Each disc carries its own set of contacts with the two sets being connected in paral lel in order that either disc may close the trip circuit The electromagnet pair are mounted face to face on opposite sides of the disc and so connected that the electrical torque of one electromagnet opposes that of ...

Page 2: ...41 181 2K 2 Figure 1a Non Tapped Type CM Relay without case Front View Figure 1b Non Tapped Type CM Relay without case Rear Vies ...

Page 3: ...3 41 181 2K Figure 2a Type CM Tapped Relay without case Front View Figure 2b Type CM Tapped Relay without case Rear View ...

Page 4: ...ont of the switch which allows the operation indicator target to drop 3 0 CHARACTERISTICS The non tapped type CM relay has a minimum pickup current of one ampere and a continuous ther mal rating of seven amperes The tapped CM relay has a minimum pickup of 1 2 or 3 amperes depend ing on the tap setting and a continuous of 7 amperes The minimum pickup current is defined as the pickup current of each...

Page 5: ...y means of the four mounting holes on the flange for the semi flush type FT case Either the stud or the mounting screws may be utilized for grounding the relay Exter nal toothed washers are provided for use in the loca tions shown on the outline and drilling plan to facilitate making a good electrical connection between the relay case its mounting screws or studs and the relay panel Ground wires a...

Page 6: ...y one ampere through the front and rear electromagnets simultaneously The moving contact should remain substantially midway between the stationary contacts A similar check should be made utilizing six amperes 4 Time Curve Contact travel is from balanced position to either the right or left stationary contacts Electromagnets are to be energized alone zero restraint Apply ten amperes and note that c...

Page 7: ...has been taken apart for repairs or the adjustments disturbed This procedure should not be used until it is apparent that the relay is not in proper working order See Acceptance Check 8 1 MAIN UNITS For all electrical checks refer to test diagram figure 5 For tapped CM put tap screw in one amp tap setting 1 Balance Setting a Mechanical balance adjust spiral spring until moving contact is located s...

Page 8: ...his value of current should not be greater than the particular ICS tap setting being used The operation indicator target should drop freely 8 3 AC INDICATING CONTACTOR SWITCH ACS Close the main relay contacts and pass sufficient ac current through the trip circuit to close the contacts of the ACS This value of current should not be greater than the particular ACS rated operating current being used...

Page 9: ...9 41 181 2K Figure 7 Internal Schematic of the Non Tapped Type CM Relay in the Type FT 31 Case Figure 8 Internal Schematic of the Tapped Type CM Relay in the Type FT 31 Case 187A232 762A812 ...

Page 10: ...41 181 2K 10 Figure 9 Element Assembly for CM Relay Front View ...

Page 11: ...11 41 181 2K Figure 10 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case Sub 4 188A144 Figure 10 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case ...

Page 12: ...ion Inc 4300 Coral Ridge Drive Coral Springs Florida 33065 TEL 954 752 6700 FAX 954 345 5329 visit our website at www abbus com papd 41 181 2K Figure 11 External Schematic Diagram of the Type CM Relay in the Type FT 31 Case 57S902 ...

Reviews: