Communication Protocols
Communication Protocols
SCADA Interface
Scada
Device Planning Parameters of the Serial Scada Interface
Parameter
Description
Options
Default
Menu path
Protocol
Select the SCADA protocol to be used. do not use,
Modbus RTU,
Modbus TCP,
Modbus TCP/RTU,
DNP3 RTU,
DNP3 TCP,
DNP3 UDP,
IEC60870-5-103,
IEC61850,
Profibus
do not use
[Device planning]
Signals (Output States) of the SCADA Interface
Signal
Description
SCADA connected
At least one SCADA System is connected to the device.
SCADA not connected
No SCADA System is connected to the device
TCP/IP Parameter
TcpIp
Global TCP/IP Parameters
Parameter
Description
Setting range
Default
Menu path
Keep Alive
Time
Keep Alive Time is the duration between two
keep alive transmissions in idle condition
1 - 7200s
720s
[Device Para
/TCP/IP
/Advanced
Settings]
Keep Alive
Interval
Keep Alive Interval is the duration between
two successive keep alive retransmissions,
if the acknowledgement to the previous
keepalive transmission was not received.
1 - 60s
15s
[Device Para
/TCP/IP
/Advanced
Settings]
188
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...