Switchgear/Breaker – Manager
Controlled Circuit Breaker
SG[1]
Direct Commands of a Controlled Circuit Breaker
Parameter
Description
Setting range
Default
Menu path
Manipulate
Position
WARNING! Fake Position - Manual Position
Manipulation
inactive,
Pos OFF,
Pos ON
inactive
[Control
/SG
/SG[1]
/General
Settings]
Res SGwear Sl
SG
Resetting the slow Switchgear Alarm
inactive,
active
inactive
[Operation
/Reset]
Ack TripCmd
Acknowledge Trip Command
inactive,
active
inactive
[Operation
/Acknowledge]
Global Protection Parameters of a Controlled Circuit Breaker
Parameter
Description
Setting range
Default
Menu path
Aux ON
The CB is in ON-position if the state of the
assigned signal is true (52a).
1..n, DI-
LogicList
DI Slot X1.DI
1
[Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]
Aux OFF
The CB is in OFF-position if the state of the
assigned signal is true (52b).
1..n, DI-
LogicList
DI Slot X1.DI
2
[Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]
Ready
Circuit breaker is ready for operation if the
state of the assigned signal is true. This
digital input can be used by some protective
elements (if they are available within the
device) like Auto Reclosure (AR), e.g. as a
trigger signal.
1..n, DI-
LogicList
-.-
[Control
/SG
/SG[1]
/Pos Indicatrs
Wirng]
404
MRI4
DOK-HB-MRI4-2E
Summary of Contents for highprotec MRI4
Page 1: ...Manual Feeder Protection MRI4 Software Version 3 4 a DOK HB MRI4 2E Revision C English...
Page 43: ...Installation and Connection 43 MRI4 DOK HB MRI4 2E...
Page 46: ...Installation and Connection Ensure the correct tightening torques 46 MRI4 DOK HB MRI4 2E...
Page 69: ...Navigation Operation Navigation Operation 69 MRI4 DOK HB MRI4 2E 1 2 3 5 7 6 8 10 9...
Page 353: ...Device Parameters 353 MRI4 DOK HB MRI4 2E...
Page 373: ...373 MRI4 DOK HB MRI4 2E...