installation instructions

LCP Series

Liquid Level Control Relays

Operation—Single Probe  

Pump Up (Fill)

: When the liquid level falls below the probe, a fixed time delay begins & the LED flashes 

Red.  This time delay prevents rapid cycling of the output relay & its load.  At the end of the time delay, the 

output relay energizes & the LED is Red ON.  The pump is ON to fill the tank.  The relay remains ener

-

gized until the liquid level rises & touches the probe.  The output relay de-energizes, turning off the pump, 

and remains de-energized & the LED is Green ON until the liquid level falls below the probe. 

 

Pump Down (Drain)

: When the liquid level rises & touches the probe, a fixed time delay begins & the 

LED flashes Red.  This time delay prevents rapid cycling of the output relay & its load.  At the end of the 

time delay, the output relay energizes & the LED is Red ON.  The pump is ON to drain the tank.  The relay 

remains energized until the liquid level falls below the probe level.  The output relay de-energizes, turning 

off the pump, and remains de-energized & the LED is Green ON until the liquid level rises & touches the 

probe.

Operation—Dual Probe

Pump Up (Fill): 

When the liquid level falls below the low level probe, a 1 second time delay begins & the 

LED flashes Red.  At the end of the time delay, the output relay energizes & the LED is Red ON.  The 

pump is ON to fill the tank.  The relay remains energized until the liquid level rises & touches the high 

level probe.  The output relay de-energizes, turning off the pump, and remains de-energized & the LED is 

Green ON until the liquid level again falls below the low level probe.

Pump Down (Drain): 

When the liquid level rises & touches the high level probe, a 1 second time delay 

begins & the LED flashes Red.  At the end of the delay, the output relay energizes & the LED is Red ON.  

The pump is ON to drain the tank.  The relay remains energized until the liquid level falls below the low 

level probe.  The output relay de-energizes, turning off the pump, and remains de-energized & the LED is 

Green ON until the liquid level rises & touches the high level probe.

If the container is non-conductive or insulated, an additional probe must be 

installed as the COM connection where it will always be submerged.

If the container is non-conductive or insulated, an additional probe must be 

installed as the COM connection where it will always be submerged.

Potentially hazardous voltages are present.  Electrical shock can cause death or serious injury.

Installation should be done by qualified personnel following all National, State & Local Codes.

BE SURE TO REMOVE ALL POWER SUPPLYING THIS EQUIPMENT BEFORE CONNECTING OR DISCONNECTING WIRING.

READ INSTRUCTIONS BEFORE INSTALLING OR OPERATING THIS DEVICE.  KEEP FOR FUTURE REFERENCE.