<11. Modbus>
11-1
IM 11Y01D01-01EN
11. Modbus
Modbus protocol can be used for TDLS8000 DCS communication. This section explains the
Modbus communication specifications that apply to the TDLS8000.
The main uses of Modbus communication on the TDLS8000 are shown below. Only a portion of
the TDLS8000 configuration function is supported.
• Checking measured values, I/O, and alarms
• Executing calibration, validation, and clock setting
• A portion of configuration functions (setting the current stream, inputting the temperature
and pressure)
11.1 Communication Specifications
The TDLS8000 can be used as a Modbus slave device. Modbus communication is possible by
connecting to a master device via Ethernet cable.
Communication standard Ethernet
Number of sessions (max.) 2
Protocol
Modbus/TCP
Port number
502
11.1.1
Message Structure
The communication message structure is shown below. The first seven bytes are the Modbus/
TCP header.
Bytes
1
Transaction ID
Modbus/TCP header
2
3
Protocol ID
4
5
Message length
6
7 Unit ID
8 Function
9
Data
:
l
Transaction ID
Data assigned by the master device to manage transactions. Slave devices simply return the
received value.
l
Protocol ID
Fixed at zero.
l
Message length
Data byte length after the unit ID.
3rd Edition: Jun. 10, 2016-00
Summary of Contents for TDLS8000
Page 10: ...ix IM 11Y01D01 01EN LT LV PL EST SLO H BG RO M CZ SK 3rd Edition Jun 10 2016 00...
Page 25: ...Blank Page...
Page 45: ...Blank Page...
Page 115: ...Blank Page...
Page 151: ...Blank Page...
Page 231: ...Blank Page...
Page 239: ...Blank Page...
Page 243: ...Blank Page...
Page 261: ...Blank Page...
Page 303: ......
Page 305: ......
Page 307: ......
Page 309: ......
Page 311: ......
Page 313: ...Blank Page...