4-40
Group 08: Protection Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
08-35
Motor
Overheat
Fault Selection
0: Disable
0
-
O
O
O
O
O
O
O
1: Deceleration to Stop
2: Free Run to top
3: Continue Running
08-36
PTC Input Filter
Time Constant
0.00 ~ 10.00
0.20
Sec
O
O
O
O
O
O
O
08-37
Fan Control
Function
0: Start in operation
0
O
O
O
O
O
O
O
1: Permanent Start
2: Start in high
temperature (except of
the models of 2050,
4100 or the above)
08-38
Delay Time of Fan
Off
0~600
60
s
O
O
O
O
O
O
O
08-39
Delay Time of
Motor Overheat
Protection
0~300
60
sec
O
O
O
O
O
O
O
08-40
Motor2
Acceleration Stall
Prevention Level
20~200
HD:150
%
O
O
O
X
X
O
O
ND:120
08-41
Motor2
Acceleration Stall
Prevention Limit
1~100
50
%
O
O
O
X
X
O
O
08-42
PTC Protection
Level
0~10.0V
0.3
V
O
O
O
O
O
O
O
08-43 PTC Restart Level 0~10.0V
1.2
V
O
O
O
O
O
O
O
08-44
PTC Warning
Level
0~10.0V
0.6
V
O
O
O
O
O
O
O
Group 09: Communication Parameters
Code Parameter Name
Setting Range
Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
09-00
INV
Communication
Station Address
1~31
1
-
O
O
O
O
O
O
O
*2
09-01
Communication
Mode Selection
0: MODBUS
0
O
O
O
O
O
O
O
*5
1: Reserved
2: Reserved
3: Reserved
4: PROFIBUS*
09-02
Baud Rate Setting
(bps)
0: 1200
4
-
O
O
O
O
O
O
O
*2
1: 2400