![TECO-Westinghouse A510 Instruction Manual Download Page 223](http://html.mh-extra.com/html/teco-westinghouse/a510/a510_instruction-manual_1072531223.webp)
4-148
Function Detection operation of frequency confirmation
Description
Output
frequency
detection
4
ON
ON
OFF
OFF
03-45
03-45
03-44
03-44
03-44
03-44
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output frequency
is below the frequency detection level
2(03-44) + frequency detection width
2(03-45) and turns off when the output
frequency falls below frequency detection
level 2(03-44).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 51 (Output
frequency detection 4).
Output
frequency
detection
5
ON
ON
OFF
OFF
03-47
03-47
03-46
03-46
03-47
03-46
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output frequency
rises above the frequency detection level
3(03-46) + frequency detection width
3(03-47) and deactivates when the output
frequency falls below frequency detection
level 3(3-46).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 52 (Output
frequency detection 5).
Output
frequency
detection
6
OFF
OFF
ON
ON
03-47
03-47
03-46
03-46
03-46
03-46
time
time
Output
Frequency
Output
Frequency
Detection 2
Signal
ON
Output is active when the output frequency
is below the frequency detection level
3(03-46) + frequency detection width
3(03-47) and turns off when the output
frequency falls below frequency detection
level 3(03-46).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 53 (Output
frequency detection 6).
Output
Frequency
Detection 1
(dedicated
for Crane)
ON
ON
OFF
OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
If the output frequency > frequency detection
level (03-13) + frequency detection width
(03-14) during acceleration, signal of output
frequency detection 1 (dedicated for Crane)
is ON.
If the output frequency < frequency detection
level (03-13) during deceleration, signal of
output frequency detection 1 (dedicated for
Crane) is OFF.
Set any parameters 03-11, 03-12 or 03-28 to
39 (output frequency detection
– dedicated
for Crane).
Frequency
Output
DC Brake
DC Brake
ON
ON
OFF
OFF
Output
Frequency
Frequency
Output
Ing
OFF
OFF
OFF
OFF
OFF
ON
ON
Run
command
Base
Block
When the inverter output frequency is active,
the output terminal is closed.