9-5
Terminal representation for 230V: 3 ~ 150 HP, 460V: 5 ~ 425HP,
575V:1~10HP, 690V:15~270HP
Connect shield to
control ground terminal
0
– 10V
+
-
Analog
Input AI2
Common/0V, GND
Control Terminals /
User Terminals
S(+)
S(-)
S1
S3
S5
S7
24V
+10V
GND
-10V
GND
DO1
DOG
S2
S4
S6
S8
24VG
F1
F2
PO
PI
GND
AO1
AI1
AO2
AI2
E
SW2
I
V
Set switch SW2
to ‘V’
9.3 Engineering Units
The PID setpoint scaling can be selected with parameter 16-03 and 16-04.
Example:
0
– 200.0 PSI Setpoint, set 16-03 to 12000 (1 decimal, range 0 – 200) and 16-04 to 2 (PSI).