11-6
600V class
Model
Horse
power
KVA
100% of rated
output current
HD/ND
Rated input current
HD/ND
Fuse rating
A510-5001-C3-U
1
1.7
1.7/3.0
1.7/3.0
10
A510-5002-C3-U
2
3
3/4.2
3/4.2
10
A510-5003-C3-U
3
4.2
4.2/5.8
4.2/5.8
10
A510-5005-C3-U
5
6.6
6.6/8.8
6.6/8.8
15
A510-5008-C3-U
7.5
9.9
9.9/12.2
9.9/12.2
20
A510-5010-C3-U
10
11.4
11.4/14.5
11.4/14.5
20
A510-6015-C3-U
15
17.9
15/19
15/19
30
A510-6020-C3-U
20
22.7
19/22
19/22
40
A510-6025-C3-U
25
26.3
22/27
22/27
40
A510-6030-C3-U
30
32.3
27/34
27/34
50
A510-6040-C3-U
40
40.
34/42
34/42
80
A510-6050-C3-U
50
50.2
42/52
42/52
80
A510-6060-C3-U
60
64.5
54/62
54/62
100
A510-6075-C3-U
75
74.1
62/80
62/80
125
A510-6100-C3-U
100
103
86/99
86/99
150
A510-6125-C3-U
125
118
99/125
99/125
200
A510-6150-C3-U
150
156
131/147
131/147
250
A510-6175-C3-U
175
175
147/163
147/163
300
A510-6215-C3-U
215
194
163/212
163/212
300
A510-6250-C3-U
270
229
192/216
192/216
400
A510-6270-C3-U
300
258
216/246
216/246
400
Fuse type:
Choose semiconductor fuse to comply with UL.
Class:
CC, J, T, RK1 or RK5
Voltage Range:
For 230V class inverter, use 300V class fuse.
For 460V class inverter, use 600V class fuse.