4-199
Notes:
If the minimum base block time (07-18) is longer than the momentary power failure time, the speed search starts
operation after the minimum base block time (07-18).
If the minimum base block time (07-18) is too short, the speed search operation begins immediately after power
has been restored.
07- 29
Run Command Selection at the Action of DC Braking
Range
0:
Not Allowable to Run
1:
Allowable to Run
When DC braking is active, then:
07-29=0:
Inverter does not run again until DC braking stops.
07-29=1:
Inverter can run again even if DC braking is in action.
07- 30
Low Voltage Level Selection
Range
0:
Disable
1:
Enable
07-30=1:
Low Voltage Detection Level (07-13) is set to 250V for 440V class Inverter and 500V for 575/690V class inverters.
07- 31
Low Voltage Run Frequency
Range
0.0~599.00 Hz
07-31=1:
When 03-00~03-07=62 (EPS Function), frequency command will be set value specified in 07-31