4-160
Timer output is turned OFF after the multi-function timer input is turned OFF for the time specified in parameter
03-38.
Timing example:
ON
ON
ON
ON
Timer input
03-37
03-38
03-37
03-38
Timer output function
03- 41
Torque Detection Level
Range
0~300
%
03-42
Brake Release Delay Time
Range
0.00~65.00 Sec
Brake Release Function
:
It is required to be with the frequency agree function, as the following figure:
When the inverter starts running, if the output frequency > 03-13, and both frequency detection level and output
torque > torque detection level (03-41), it will delay the time of 03-42 to release brake.
Motor Speed
(Output Frequency)
t
03-42
Brake Release delay time
03-42
Brake Release delay time
Output Freq.> 03-13
and
Output Torque > 03-41
DO 03-11
、
03-12
、
03-28
set 38 Brake Release
Output Freq.< 03-13
or
Output Torque < 03-41
It is recommended to be with starting and stopping frequency locked function (11-43~11-46), shown as the
following figure: