4-77
00-00=2: Sensorless Vector Control
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor
parameters for higher performance operation. Perform non-rotational auto-
tune if it’s not possible to rotate the
motor during auto-tune. Refer to parameter group 17 for details on auto-tuning.
00-00=3: Closed Loop Vector Control
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor
parameters for higher performance operation. Perform non-rotational auto-
tune if it’s not possible to rotate the
motor during auto-tune. Refer to parameter group 17 for details on auto-tuning.
00-00=4: PM Vector Control
Verify the inverter rating matches the motor rating. Set PM motor data in parameters 22-00 to 22-06 and encoder
feedback pulses in parameter 20-27. Refer to parameter 22-21 for details on PM Motor tuning.
Select the appropriate motor rating and braking resistor based on your motor and applications. Please install the
braking module in the models of 200V 30HP/ 400V 40HP/575V/690V 50HP or the above.
00-00=5: PM Sensorless Vector Control
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor
parameters for higher performance operation.
Perform auto-tuning before operation to enhance the performance of PMSLV mode. Refer to parameter 22-21 for
the descriptions of PM motor tuning function.
Select the appropriate motor rating and braking resistor based on your motor and applications. Please install the
braking module in the models of 200V 30HP/ 400V 40HP/575V/690V 50HP or the above.
00-00=6: SLV2 Vector Control
Verify the inverter rating matches the motor rating. Perform rotational auto-tune to measure and store motor
parameters for higher performance operation.
Refer to parameter group 17 for the descriptions of motor parameter tuning function.
Select the required V/F curve (01-00) based on your motor and applications.
Note:
Parameter 00-00 is excluded from initialization.
00-01
Motor
’s rotation direction
Range
0:
Forward
1:
Reverse
Use the FWD/REV key to change motor direction when Run Command Selection (00-02 = 0) is set to keypad
control.
00-02
Run command selection
Range
0:
Keypad control
1:
External terminal control
2:
Communication control
3:
PLC